| Brand Name: | Hailos |
| Model Number: | L15 |
| MOQ: | 1 |
| Price: | $3000~$8000 |
| Delivery Time: | 5-8 weeks |
| Payment Terms: | T/T |
| Model | LXXAW | L12 | L25 | L35 | L40 | ||
| Cooling capacity |
Capacity | KW | 12.5 | 25.2 | 38.2 | 42.5 | |
| Sensible cooling caacit |
KW | 12.5 | 25.2 | 38.2 | 42.5 | ||
| Sensibleheat | 1 | 1 | 1 | 1 | |||
| factor compressor |
Variablefrequency rotor compressor | Variablefrequencyvortex compressor | |||||
| Compressor | Fan type | EC axial / EC centrifugal | EC axial / EC centrifugal | EC centrifugal | EC centrifugal | ||
| Air flow | m3/h | 3200 | 5500 | 8200 | 10000 | ||
| ventilation patte | Rear return air Frontal air supply, can be configuredwithfield adjustabledirection winddeflector, can realizehorizontal air supplyfrom thefront,horizontal air supplyfrom the left side, horizontal air supplyfrom the right side, andhorizontal air supplyfrom the left and right sides |
||||||
| expansionvalve | Electronic | ||||||
| Refrigerant | R410a | ||||||
| selective assembly |
heating capacity | KW | 3 | 3 | 6 | 6 | |
| humidification amount |
Kg/h | 3 | 3 | 3 | 3 | ||
| Unit size | Width | mm | 300 | 300 | 600 | 600 | |
| Length | mm | 1200 | 1200 | 1200 | 1200 | ||
| Height | mm | 2000 | 2000 | 2000 | 2000 | ||
| Connection pipe |
Air pipe | mm | φ16 | φ19 | φ22 | φ22 | |
| Liquid pipe | mm | φ12 | φ16 | φ16 | φ16 | ||
| Drain pipe | mm | φ19 | φ19 | φ19 | φ19 | ||
| Humidifier waterin | let pipe | G1/2" | G1/2" | G1/2" | G1/2" | ||
| Weight | Kg | 260 | 295 | 390 | 420 | ||
| Distribution parameter W |
Power supply | 380V3Ph-50Hz | |||||
| Recommended circuit breaker |
D32 | D40 | D63 | D63 | |||
| iring specification | mm2 | 6 | 10 | 10 | 10 | ||
| Outdoor unit |
Model | SCW181 | SCW48E | SCW48E | SCW55E | ||
| Quantity | 1 | 1 | 2 | 2 | |||
| Weight | Kg | 60 | 125 | 125 | 145 | ||
| Wiring specificatio | mm2 n |
1.5 | 2.5 | 2.5 | 2.5 | ||
| Vertical mounting |
W | mm | 850 | 850 | 850 | 850 | |
| L | mm | 550 | 550 | 550 | 550 | ||
| H | mm | 800 | 1600 | 1600 | 1600 | ||
| Remark | 1. Test conditions: return air temperature 37°C, relative humidity 24%; 2. The depth dimension can be extended to 1200mm, and the height dimension can be extended to 2200mm; 3. The outdoor unit is selected according to the inlet air temperature of 35°C. For other operating environments, please contact our company; 4. When the equivalent distance of the connecting pipe exceeds 30m, please refer to the installation specification to increase the pipe diameter; 5. If the data is not listed in the data sheet, please contact our company; 6. If you have other customized needs, please contact our company. |
||||||
![]()
![]()
![]()
![]()
![]()
![]()
Project Case
![]()